Your Flow Meter Experts
1-888-722-5543

Display - Flow Rate / Total Pulse input.

Brand: | Part #: PD6300-6R0 | Item #: ID16380
PD6300-6R0:  Flow Rate / Totalizer Meter Pulse Input 85-265Vac powered - no options . Panel Mount. Nema 4, IP65 front.
Popular models in stock
Check Availability
Price: $329.00
The PD6300 is s 1/8 DIN flow,rate and totalizing meter for analog output transmitters. They can display flow rate and flow total at the same time, provide excitation power for the flowmeter. Displays total, grand total, or non-resettable total on up to nine digits.

Inputs: Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kO pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 kO pull-up to 5 V @ 40 Hz; coil (sine wave) 40 mVp-p min @ 10 kHz; Modbus PV (Slave)
Low Voltage Mag Pickup (Isolated): Sensitivity: 40 mVp-p to 8 Vp-p
Minimum Input Frequency: 0.001 Hz - Minimum frequency is dependenton high gate setting.
Maximum Input Frequency: 30,000 Hz (10,000 for Low Voltage Mag Pickup)
Input Impedance: Pulse input: Greater than 300 kO @ 1 kHz. Open collector/switch input: 4.7 kO pull-up to 5 V.
Accuracy: ±0.03% of calibrated span ±1 count
Display Update Rate: Total: 10/sec, Rate: 10/sec to 1/1000 sec
Temperature Drift: Rate display is not affected by changes in temperature.
Multi-Point Linearization: 2 to 32 points
Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd.
Calibration: May be calibrated using K-factor, scale using internal calibration, or calibrate by applying an external calibration signal.
K-Factor: Field programmable K-factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit.
Calibration Range: Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above setting.
Filter: Programmable contact de-bounce filter, 40 to 999 Hz maximum input frequency allowed with low speed filter.
Time Base: Second, minute, hour, or day
Low Gate: 0.1-99.9 seconds
High Gate: 2.0-999.9 seconds

Data Sheets

Manuals

Recommended Accessories

Plastic NEMA 4X Enclosure for 1 Meter
PDA2811 :  Low-Cost Plastic NEMA 4X Enclosure for 1 Meter.
Brand: | Part #: PDA2811 | Item #: ID2519